MODEL | NES-100-5 | NES-100-7.5 | NES-100-9 | NES-100-12 | NES-100-15 | NES-100-24 | NES-100-48 |
UITVOER | GELIJKSPANNING | 5 V. | 7, 5 V. | 9 V. | 12 V. | 15 V. | 24 VOLT | 48 V. |
NOMINALE STROOM | 20 A. | 13, 6 A. | 11, 2 A. | 8.5A | 7 A. | 4.5A | 2.3A |
STROOMBEREIK | 0 ~ 20A | 0 ~ 13, 6A | 0 ~ 11, 2 A. | 0 ~ 8, 5A | 0 ~ 7A | 0 ~ 4, 5A | 0 ~ 2, 3A |
NOMINAAL VERMOGEN | 100 W. | 102 W. | 100, 8 W | 102 W. | 105 W. | 108 W. | 110, 4 W. |
RIMPEL en GELUID (max. ) Opmerking. 2 | 80 mVp-p | 120 mVp-p | 120 mVp-p | 120 mVp-p | 120 mVp-p | 120 mVp-p | 150 mVtt |
SPANNING ADJ. BEREIK | 4.75 ~ 5, 5 V. | 7.13 ~ 8, 3 V. | 8.55 ~ 9, 9 V. | 11.4 ~ 13, 2 V. | 14.25 ~ 16, 5 V. | 22.8 ~ 26, 4 V. | 45.6 ~ 52, 8 V. |
OPMERKING OVER DE SPANNINGSTOLERANTIE. 3 | ±2.0% | ±1.0% | ±1.0% | ±1.0% | ±1.0% | ±1.0% | ±1.0% |
OPMERKING OVER DE REGELING VAN DE LIJN . 4 | ±0.5% | ±0.5% | ±0.5% | ±0.5% | ±0.5% | ±0.5% | ±0.5% |
OPMERKING OVER DE BELASTINGSREGELING . 5 | ±0.5% | ±0.5% | ±0.5% | ±0.5% | ±0.5% | ±0.5% | ±0.5% |
INSTELLEN, STIJGTIJD | 1000 ms, 20 ms/230 VAC 1000 ms, 20 ms/115 VAC bij vollast |
STOPTIJD (NORMAAL) | 30 ms/230 VAC 25 ms/115 VAC bij vollast |
INVOER | SPANNINGSBEREIK | 85 ~ 132 VAC / 176 ~ 264 VAC geselecteerd door schakelaar 248 ~ 373 VDC |
FREQUENTIEBEREIK | 47 ~ 63 Hz |
EFFICIËNTIE (normaal) | 80% | 81% | 81% | 83% | 84% | 86% | 86% |
AC-STROOM (normaal) | 2 A/115 VAC 1, 2 A/230 VAC |
INSCHAKELSTROOM (normaal) | KOUDE START 45A |
LEKSTROOM | < 2 mA / 240 VAC |
BESCHERMING | OVERBELASTING | 110 ~ 150% nominaal uitgangsvermogen |
Type bescherming: De modus "hiccup", herstelt automatisch na het verhelpen van de storing |
OVERSPANNING | 5.75 ~ 6, 75 V. | 8.6 ~ 10, 1 V. | 10.4 ~ 12, 2 V. | 13.8 ~ 16, 2 V. | 17.25 ~ 20, 25 V. | 27.6 ~ 32, 4 V. | 55.2 ~ 64, 8 V. |
Type bescherming: De modus "hiccup", herstelt automatisch na het verhelpen van de storing |
MILIEU | WERKTEMPERATUUR | -20 ~ +60ºC (zie „derating Curve”) |
BEDRIJFSVOCHTIGHEID | 20 ~ 90% relatieve luchtvochtigheid, niet-condenserend |
OPSLAGTEMPERATUUR, VOCHTIGHEID | -40 ~ +85 ºC, 10 ~ 95% RV |
TEMP. COËFFICIËNT | ±0.03%/ºC (0 ~ 50ºC) |
TRILLINGEN | 10 ~ 500 Hz, 2 G 10 min. /1 cyclus, periode 60 min. Elk langs X-, Y-, Z-assen |
VEILIGHEID EN | VEILIGHEIDSSTANDAARDEN Opmerking. 6 | UL60950-1, CB (IEC60950-1), CCC GB4943.1: 2011 GOEDGEKEURD |
EMC | WEERSTANDSSPANNING | I/P-O/P: 3KVAC I/P-FG: 2KVAC O/P-FG: 0, 5KVAC |
(Opmerking 7) | ISOLATIEWEERSTAND | I/P-O/P, I/P-FG, O/P-FG: 100 OHM / 500 VDC / 25 ºC / 70% RELATIEVE LUCHTVOCHTIGHEID |
| EMC-EMISSIE | Voldoet aan EN55022 (CISPR22) Klasse B, EN61000-3-2, -3 |
| EMC-IMMUNITEIT | Voldoet aan EN61000-4-2, 3, 4, 5, 6, 8, 11, EN55024, EN61000-6-1, licht industrieniveau, criteria A |
ANDERE | MTBF | 320, 7 kuur min. MIL-HDBK-217F (25 ºC) |
AFMETING | 159*97*38 MM (L*B*H) |
PAKKING | 0, 55 kg; 30 stuks/17, 5 kg/0, 97 CUFT |
OPMERKING | 1. Alle niet speciaal genoemde parameters worden gemeten bij een ingangsvermogen van 230 VAC, nominale belasting en een omgevingstemperatuur van 25 ºC. 2. Ripple $ ruis wordt gemeten bij 20 MHz bandbreedte door gebruik te maken van een tweederde paar-draad van 12 inch met een parallelle caacitor van 0, 1uf en 47uf. 3. Tolerantie: Omvat insteltolerantie, lijnregeling en belastingsregeling. 4. De lijnregeling wordt gemeten van lage tot hoge lijn bij nominale belasting. 5. De belastingsregeling wordt gemeten van 0% tot 100% nominale belasting. 6. Op verzoek van GB4943.1 is de stroomvoorziening alleen geschikt voor gebruik op de hoogte van 2000 m lager en in de niet-tropische klimaatomstandigheden. 7. De voeding wordt beschouwd als een onderdeel dat in een eindapparatuur zal worden geïnstalleerd. De uiteindelijke apparatuur moet opnieuw worden bevestigd dat deze nog steeds voldoet aan de EMC-richtlijnen. Raadpleeg „EMI-testen van de voedingen van componenten” voor richtlijnen over het uitvoeren van deze EMC-tests. (zoals beschikbaar op http: //yawaled. en. made-in-china. com ) |