Tabel 1 type PR211 |
S. Nr. |
Functie |
Instellingen |
Type |
PR211 |
PR211 |
PR211 |
PR211 |
Reset van de factroy |
Polen |
3-PINS |
3-PINS |
3-PINS |
3-PINS |
Score (A) |
250 |
400 |
800 |
1600 |
1 |
L |
Instelling overbelastingsstroom (A) |
(0.4, 0.5, 0.6, 0.7, 0.8, 0.9, 0.95, 1.0)Xin |
(0.4, 0.5, 0.6, 0.7, 0.8, 0.9, 0.95, 1.0)Xin |
(0.4, 0.5, 0.6, 0.7, 0.8, 0.9, 0.95, 1.0)Xin |
(0.4, 0.5, 0.6, 0.7, 0.8, 0.9, 0.95, 1.0)Xin |
1, 0 inch |
2 |
Instelling vertraging bij overbelasting stroom |
3S, 6S, 12S, 18S |
3S, 6S, 12S, 18S |
3S, 6S, 12S, 18S |
3S, 6S, 12S, 18S |
3 SEC. |
3 |
IK |
Instelling van de huidige stroom |
(1.5, 2, 4, 6, 8, 10, 12, UIT)Xin |
(1.5, 2, 4, 6, 8, 10, 12, UIT)Xin |
(1.5, 2, 4, 6, 8, 10, 12, UIT)Xin |
(1.5, 2, 4, 6, 8, 10, 12, UIT)Xin |
10 inch |
Tabel 2 type PR212 |
S. Nr. |
Functie |
Instellingen |
Type |
PR212 |
PR212 |
PR212 |
PR212 |
Reset van de factroy |
Polen |
3-PINS |
3-PINS |
3-PINS |
3-PINS |
Score (A) |
250 |
400/630 |
800 |
1600 |
1 |
L |
Instelling overbelastingsstroom (A) |
(0.4, 0.5, 0.55, 0.6, 0.65, 0.7, 0.75, 0.8)Xin |
(0.4, 0.5, 0.55, 0.6, 0.65, 0.7, 0.75, 0.8)Xin |
(0.4, 0.5, 0.55, 0.6, 0.65, 0.7, 0.75, 0.8)Xin |
(0.4, 0.5, 0.55, 0.6, 0.65, 0.7, 0.75, 0.8)Xin |
1, 0 inch |
2 |
Instelling vertraging bij overbelasting stroom |
3S, 6S, 12S, 18S |
3S, 6S, 12S, 18S |
3S, 6S, 12S, 18S |
3S, 6S, 12S, 18S |
3 SEC. |
3 |
S |
Kortsluiting - instelling stroomsterkte stroomkring (A) |
(1, 2, 3, 4, 6, 8, 10, UIT) Xin |
(1, 2, 3, 4, 6, 8, 10, UIT) Xin |
(1, 2, 3, 4, 6, 8, 10, UIT) Xin |
(1, 2, 3, 4, 6, 8, 10, UIT) Xin |
6 inch |
4 |
Tijdsvertraging bij instelling kortsluitstroom |
0.05, 0.1, 0.25, 0.5 |
0.05, 0.1, 0.25, 0.5 |
0.05, 0.1, 0.25, 0.5 |
0.05, 0.1, 0.25, 0.5 |
0.1S |
5 |
IK |
Instelling van de huidige stroom |
(1.5, 2, 4, 6, 8, 10, 12, UIT)Xin |
(1.5, 2, 4, 6, 8, 10, 12, UIT)Xin |
(1.5, 2, 4, 6, 8, 10, 12, UIT)Xin |
(1.5, 2, 4, 6, 8, 10, 12, UIT)Xin |
10 inch |
6 |
G |
Instelling aardfout stroom (A) |
(0.2, 0.3, 0.4, 0.6, 0.8, 0.9, 1.0, UIT)Xin |
(0.2, 0.3, 0.4, 0.6, 0.8, 0.9, 1.0, UIT)Xin |
(0.2, 0.3, 0.4, 0.6, 0.8, 0.9, 1.0, UIT)Xin |
(0.2, 0.3, 0.4, 0.6, 0.8, 0.9, 1.0, UIT)Xin |
1, 0 inch |
7 |
Instelling vertraging bij aardfout |
0.1, 0.2, 0.4, 0.8 |
0.1, 0.2, 0.4, 0.8 |
0.1, 0.2, 0.4, 0.8 |
0.1, 0.2, 0.4, 0.8 |
0.4S |
8 |
|
Selectie van elektrische of elektronische parameters ingesteld |
Functie INGESTELD (schakelaar ELT/MAN) |
9 |
|
Gebruikt voor het instellen van parameters van de dip-schakelaar van nullijn |
Inn=%in, switch 50/100 |
10 |
|
Aansluiting voor meetapparaat |
Paneelaansluiting |