Basis Informatie.
Toepassing
Bouw, Boven het hoofd, Ondergronds, Industrieel, Centrale
Voltage
Laag-en middenspanning Kabel
Materiaal Vorm
Ronde Wire
Wire Core Material
Bare koperdraad
Certificaat
ISO, CCC, CE, RoHS, VDE
Beschrijving
APPLICATION
The cables is mainly used in power stations, mass transit underground passenger systems, airports,
petrochemical plants, hotels, hospitals, and high-rise buildings.
STANDARDS
Basic design to BS 5308
FIRE PERFORMANCE
Flame Retardance (Single Vertical Wire Test) | EN 60332-1-2; IEC 60332-1-2; BS EN 60332-1-2; VDE 0482-332-1 ; NBN C 30-004 (cat. F1); NF C32-070-2.1(C2); CEI 20-35/1-2; EN 50265-2-1*; DIN VDE 0482-265-2-1* |
Reduced Fire Propagation (Vertically-mounted bundled wires & cable test) | EN 60332-3-24 (cat. C); IEC 60332-3-24; BS EN 60332-3-24; VDE 0482-332-3; NBN C 30-004 (cat. F2); NF C32-070-2.2(C1); CEI 20-22/3-4; EN 50266-2-4*; DIN VDE 0482-266-2-4 |
Halogen Free | IEC 60754-1; EN 50267-2-1; DIN VDE 0482-267-2-1; CEI 20-37/2-1 ; BS 6425-1* |
No Corrosive Gas Emission | IEC 60754-2; EN 50267-2-2; DIN VDE 0482-267-2-2; CEI 20-37/2-2 ; BS 6425-2* |
minimum Smoke Emission | IEC 61034-1&2; EN 61034 -1&2; DIN VDE 0482-1034-1&2; CEI 20-37/3-1&2; EN 50268-1&2*; BS 7622-1&2* |
No Toxic gases | NES 02-713; NF C 20-454 |
Note: Asterisk * denotes superseded standard.
VOLTAGE RATING
300/500V
CABLE CONSTRUCTION
Conductor: Plain annealed copper wire, stranded according to IEC(EN) 60228 class 2.
Insulation: Extruded cross-linked XLPE compound.
Filler, binder(if any): PP, Mylar tape
Circuit Protective Conductor: Annealed plain copper (class 2)
Overall Screen: Aluminium/polyester tape
Outer Sheath: Thermoplastic LSZH compound type LTS3 as per BS 7655-6.1 (Thermosetting LSZH
compound type SW2-SW4 as per BS 7655-2.6 can be offered.)
COLOUR CODE
Insulation colour as per bs7671
| with earth conductor | without earth conductor |
2Cores | - | Brown,Blue |
3Cores | Yellow/Green,Brown,Blue | Brown,Gray,Black |
4Cores | Yellow/Green,Brown,Gray,Black | Brown,Gray,Black,Blue |
5Cores | Yellow/Green,Brown,Gray,Black,Blue | Brown,Gray,Black,Blue,Black |
above 5 Cores | Yellow/Green,Black Numbered | Black Numbered |
sheath colour: Black
Physical AND THERMAL PROPERTIES
Temperature range during operation: Max.90°C for XLPE
250°C in short-circuit for 5s max.
Minimum bending radius: 6 x Overall Diameter
CONSTRUCTION PARAMETERS
Conductor | FTX200 05ROZ1-R |
No. Of Core X Cross Section | No./ Nominal Diameter Of Strands | Nominal Overall Diameter Conductor | Nominal Insulation Thickness | Cross- Section Area Of Circuit Protective Conductor | Nominal Sheath Thickness | Nominal Overall Diameter | Max.Dc Resistance Of Conductor @20°C | Approx. Weight |
Noxmm2 | No./mm | mm | mm | mm2 | mm | mm | Ω/km | Kg/km |
7x1.0 | 7i0.44 | 1.32 | 0.6 | 1.0 | 1.0 | 11.2 | 18.1 | 186 |
7x1.5 | 7i0.53 | 1.59 | 0.7 | 1.5 | 1.1 | 12.9 | 12.1 | 253 |
7x2.5 | 7i0.67 | 2.01 | 0.8 | 2.5 | 1.2 | 14.9 | 7.41 | 365 |
12x1.5 | 7i0.53 | 1.59 | 0.7 | 1.5 | 1.2 | 16.8 | 12.1 | 404 |
12x2.5 | 7i0.67 | 2.01 | 0.8 | 2.5 | 1.4 | 19.8 | 7.41 | 595 |
19x1.5 | 7i0.53 | 1.59 | 0.7 | 1.5 | 1.3 | 19.7 | 12.1 | 600 |
19x2.5 | 7i0.67 | 2.01 | 0.8 | 2.5 | 1.5 | 23.2 | 7.41 | 885 |
Electrical PROPERTIES
Conductor Operating Temperature : 90°C
Ambient Temperature : 30°C
Current-Carrying Capacities (Amp)
Conductor cross- sectional area | Reference method 4 (enclosed in conduit in thermally insulating wall etc) | Reference method 3 (enclosed in conduit on a wall or in trunking etc) | Reference method 1 (clipped direct) | Reference method 11 (on a perforated cable tray, horizontal or vertical) | Reference method 12 (free air) |
Horizontal flat spaced | Vertical flat spaced | Trefoil |
2 cables, single- phase a.c. or d.c. | 3 or 4 cables, 3-phase a.c. | 2 cables, single- phase a.c. or d.c | 3 or 4 cables, 3-phase a.c. | 2 cables, single- phase a.c. or d.c. flat and touching | 3 or 4 cables, 3-phase a.c. flat and touching or trefoil | 2 cables, single- phase a.c. or d.c. or flat and touching | 3 or 4 cables, 3-phase a.c. flat and touching or trefoil | 2 cables, single- phase a.c. or d.c. or 3 c ables three phase | 2 cables, single- phase a.c. or d.c. or 3 cables three phase | 3 cables, trefoil 3-phase a.c. |
1 | 2 | 3 | 4 | 5 | 6 | 7 | 8 | 9 | 10 | 11 | 12 |
mm2 | A | A | A | A | A | A | A | A | A | A | A |
1.5 | 18 | 17 | 22 | 19 | 25 | 23 | - | - | - | - | - |
2.5 | 24 | 23 | 30 | 26 | 34 | 31 | - | - | - | - | - |
Voltage Drop (Per Amp Per Meter)
Nominal Cross Section Area | 2 cables d.c. | 2 cables, single-phase a.c. | 3 or 4 cables, 3-phase a.c. |
Ref. Methods 3 and 4 (enclosed in conduit etc, in or on a wall) | Ref. Methods 1 and 11 (clipped direct or on trays touching) | Ref. Methods 3 and 4 (enclosed in conduit etc, in or on a wall) | Ref. Methods 1, 11 and 12 (in trefoil) | Ref. Methods 1 and 11(Flat and touching) |
1 | 2 | 3 | 4 | 5 | 6 | 7 |
mm2 | mV/A/m | mV/A/m | mV/A/m | mV/A/m | mV/A/m | mV/A/m |
1.5 | 31 | 31 | 27 | 27 | 27 | 27 |
2.5 | 19 | 19 | 16 | 16 | 16 | 16 |
Adres:
Room3501, Citic Square, 1168nanjing Xi Lu, 200041, Shanghai, China
Soort bedrijf:
Fabrikant/fabriek
Zakelijk Bereik:
Elektrotechniek & Elektronica's
Bedrijfsintroductie:
Addison bekabelingssysteem, ontstaan als netwerkbekabelingssysteem dat op de markt wordt gebracht door Caledonian Cables Ltd, gevestigd in Sussex, Engeland. Caledonian Cable, opgericht in 1978, trad oorspronkelijk op de markt als OEM-fabrikant van kabelsystemen.
In de jaren negentig was Caledonian strikt een OEM-fabrikant van kabels en patchkabels voor de prestigieuze kabelbedrijven in Europa.
In 1997 trad Caledonian toe tot de markt voor databekabeling met complete oplossingen onder Addison voor de twisted pair netwerkomgeving. In 1998 kwam Caledonian uit als een van de veelbelovende fabrikanten van OEM-kabeloplossingen in Europa.
Het Adsoon OMS Network Cabling System bestaat uit een horizontaal netwerkbekabelingssysteem, een verticaal netwerkbekabelingssysteem, een backbone-netwerkbekabelingssysteem en een bekabelingssysteem voor het werkgebied, enz.